Directions for use
Dosage and Control
The condensate is tested for pH to determine the dosage level. The pH limits are 8.5-9.2. For an average system e.g. 10 m3, the dosage is approximately 0.65 ltr/day
Dosing Method
NALFLEET™ Condensate Control is best dosed continuously using an automatic dosing unit. The treatment can be dosed together with the oxygen scavenger.
Suitable dosage points are:
- Boiler feed line after recirculation valve
- Condensate pump discharge NALFLEET™ Condensate Control can be fed using an automatic dosing system. Consult your WSS representative for specific dosing instructions.
Sampling and Testing
A representative sample of condensate should be drawn for analysis daily. The sample should always be taken from the same point, cooled and tested immediately. Follow the test kit instructions and log the results in Waterproof. The results should be sent to WSS as stated in the Waterproof instructions.
Condensate Control Dosing Parameters (all pressure groups)
Standard pH range is 8.5 to 9.2
Measured pH
If pH < 8.5: Increase Dosage by 25%. Retest after 24 hrs or shorter. If pH within 8.5 to 9.2: Within control. No adjustment needed, continue with routine monitoring. If pH > 9.2: Decrease dosage by 25%. Retest after 24 hrs or shorter.
These are recommended values based on experience and are in no way intended to replace the boiler manufacturer’s specifications or company regulations.
It is important that regular testing is carried out to ensure levels of treatment are correct. Use dosage chart to maintain condensate pH between 8.5-9.2.